15 Miss. Code R. § 16-1-51.81.12

Current through June 25, 2024
Rule 15-16-1-51.81.12 - Doors

All doors in corridors shall be 20-minutes fire rated floors (1-3/4" solid core wood door as a minimum). All doors to patient bedrooms, diagnostic and treatment areas, and other doors used by residents shall be at least 36" wide. No door shall swing into the corridor except closet doors. to hazardous areas defined in the Life Safety Code shall be 1-1/2 hours "B" labeled fire doors. Exit doors shall conform to the requirements set forth in the Life Safety Code.

15 Miss. Code. R. § 16-1-51.81.12

Miss. Code Ann. § 43-11-13