Rule 15-16-1-41.9.10 - Elevators

One power driven elevator is required in all hospitals having patient rooms, operating suite, or delivery suite above the first floor. Two or more elevators are required if 60 or more patients are housed above the ground floor. Minimum cab dimensions required for elevators transporting patients is 76" x 50" inside clear measurements; hatchway and cab doors 3'8" wide, minimum. are subject to the requirements of referenced standard listed in paragraph 602, Codes, of this regulation.