Rule 15-16-1-1.47.25 - Smoke Barrier or Fire-Retardant Walls

Each building shall be divided into areas not exceeding five thousand (5,000) square feet between exterior walls or smoke barrier walls. The barrier walls shall be constructed from floor to roof decking with no openings except in corridors or other areas specifically approved by the licensing agency. Selfclosing "B" label fire doors with fusible linkage shall be installed in the barrier walls in corridors. All air spaces in the walls shall be filled with noncombustible material. The current edition of NFPA 101 Life Safety Code (recognized by licensing agency) shall be the governing code for smoke barrier or fire-retardant walls items which are not covered in the regulations.