"EVACUATION, IMPRACTICAL. The movement of all occupants, residents and staff to an exit in more than 13 minutes."
"EVACUATION, SLOW. The movement of all occupants, residents and staff to an exit in more than 3 minutes, but not more than 13 minutes."
"NIGHTCLUB. All buildings and places of public assembly designed for use as dance halls, eating and/or drinking establishments, and similar occupancies, in which the established maximum permitted occupant load exceeds the number of seats provided by more than 30 percent or which affords less than 12 square feet net area per occupant. For purposes of determining the net area per occupant, only the actual public assembly room or rooms shall be considered. For purposes of applying the requirements of this code, the nightclub shall include all rooms, lobbies and other spaces connected thereto with a common means of egress and entrance."
"RADIOACTIVE MATERIAL. Any material or combination of materials that spontaneously emit ionizing radiation."
"RESIDENTIAL HEALTH CARE FACILITY. A facility not located with, and operated by, a licensed health care facility that provides food, shelter, supervised health care and related services, in a homelike setting, to four or more persons 18 years of age or older who are unrelated to the owner or administrator."
"SINGLE RESIDENTIAL OCCUPANCY: A building arranged or used for individual non-transient residency by persons living independently of one another, regardless of whether the residents share the use of common facilities, such as kitchen or bathing facilities."
Radioactivej | 25 REM unsealed source 100 REM sealed source | 100 REM sealed d source | 25 REM sealed source |
j Maximum dosage allowed in any single whole-body short-term (1 hour or less) exposure.
Additionally, the list of occupancies shall be deleted in its entirety and the following list inserted:
"Hotels
Motels
Vacation timeshare properties"
Care facilities that provide accommodations for five or fewer persons receiving care;
Single residential occupancies, accessory to a dwelling unit, having no more than five roomers or lodgers. (Single occupancies, accessory to a dwelling unit, having more than five roomers or lodgers shall be classified as Group R-2 or I-1, as appropriate.);
Group Homes with 5 or fewer occupants in accordance with Section 308.2.4;
Rooming houses with five or fewer residents;
Cooperative sober living residences with not more than 10 occupants, excluding staff; each occupant, including staff, shall be capable of prompt evacuation."
Automatic Sprinkler System Thresholds
Group B | |||
IIB | IIIB | VB | |
Story | Max. Area | Max. Area | Max. Area |
1 | 36,000 | ||
2 | 72,000 (36,000 per floor) | ||
3 | 99,360 (36,000 per floor) | 99,360 (36,000 per floor) | |
Group F-2 | |||
IIB | IIIB | VB | |
Story | Max. Area | Max. Area | Max. Area |
1 | 36,000 | 18,000 | |
2 | 72,000 (36,000 per floor) | 36,000 (18,000 per floor) | |
3 | 99,360 (36,000 per floor) | ||
Group S-2 | |||
IIB | IIIB | VB | |
Story | Max. Area | Max. Area | Max. Area |
1 | 36,000 | 36,000 | 18,000 |
2 | 72,000 (36,000 per floor) | 72,000 (36,000 per floor) | 36,000 (18,000 per floor) |
3 | 99,360 (36,000 per floor) | 99,360 (36,000 per floor) |
Requirements as set forth in this code
Exception: An approved indicating control valve supervised in the open position in accordance with Section 903.4.
Exception: The residual pressure of 65 psi (448 kPa) is not required in buildings equipped throughout with an automatic sprinkler system installed in accordance with either Section 903.3.1.1 or 903.3.1.2 and also where the highest floor level is not more than 150 feet (45720 mm) above the lowest level of fire department vehicle access.
Exceptions:
Exceptions
Exceptions:
Exceptions:
Exceptions:
Also, renumber Items 3 through 6 as 2 through 5. Lastly, in Item #5, "fire code official" shall be deleted and "fire protection subcode official" shall be inserted.
Exception: Automatic fire detection systems are not required in buildings provided with an automatic sprinkler system throughout."
Exceptions:
Section 907.5.2.2.5 , Emergency power. Emergency voice/alarm communications systems shall be provided with emergency power in accordance with Section 2702. The system shall be capable of powering the required load for a duration of not less than 24 hours, as required in NFPA 72.
"Exceptions
Exception: Fire protection systems in high rise buildings designed with a low zone and a high zone may be provided with a connection for each zone."
lxxxiv. In 915.1.2, Fuel-burning appliances and fuel-burning fireplaces, the word "and" shall be deleted before "classrooms" and the words "or any other occupiable space(s)" shall be added following "classrooms."
Exception: Carbon monoxide detection equipment shall not be required in locations, such as repair garages, where the presence of carbon monoxide may be expected as a function of the normal use of the space. Additionally, carbon monoxide detection equipment shall not be required in locations where battery charging for motorized equipment takes place. In such locations, carbon monoxide detection equipment shall be provided just outside such spaces at the points where these spaces connect to other occupiable space(s)."
PENALTY
$ 250 FIRST OFFENSE
SUBSEQUENT OFFENSES
$ 250 MINIMUM AND/OR
UP TO 90 DAYS COMMUNITY SERVICE
TOW AWAY ZONE
Exception: The number of Type A units is permitted to be reduced in accordance with 1108.7.
Exception: The number of Type A units is permitted to be reduced in accordance with 1108.7.
"Exceptions:
"Exceptions:
" Section 1113. Variations
"Exceptions:
N.J. Admin. Code § 5:23-3.14