Current through Bulletin No. 2024-21, November 1, 2024
Section R432-11-2 - General Construction(1) The licensee shall additionally comply with Section R432-4-19 and ensure compliance with the following modifications:(a) corridors in patient use areas are a minimum of eight feet wide;(b) handrails are provided on both sides of corridors and hallways used by patients that are 34 inches above the floor, except for areas serving children and other special care areas; and(c) fixtures in a resident toilet and bathroom are wheelchair accessible with wheelchair turning space within the room.(2) The licensee shall provide the following:(a) plumbing, including medical gas and suction systems;(b) an emergency electrical service;(c) an onsite emergency generator connected to the recommended services in the plans review required in Section R432-4-12;(f) heating equipment necessary to provide adequate heated space to house all patients under emergency conditions;(g) one duplex receptacle in each patient room;(h) one duplex receptacle at each nurse station;(i) duplex receptacles in the emergency heated area at a ratio of one for each ten patients; and(j) fuel storage capacity that permits continuous operation for at least 48 hours.Utah Admin. Code R432-11-2
Amended by Utah State Bulletin Number 2023-15, effective 7/26/2023