40 C.F.R. § 280.44

Current through March 31, 2024
Section 280.44 - Methods of release detection for piping

Each method of release detection for piping used to meet the requirements of § 280.41 must be conducted in accordance with the following:

(a)Automatic line leak detectors. Methods which alert the operator to the presence of a leak by restricting or shutting off the flow of regulated substances through piping or triggering an audible or visual alarm may be used only if they detect leaks of 3 gallons per hour at 10 pounds per square inch line pressure within 1 hour. An annual test of the operation of the leak detector must be conducted in accordance with § 280.40(a)(3) .
(b)Line tightness testing. A periodic test of piping may be conducted only if it can detect a 0.1 gallon per hour leak rate at one and one-half times the operating pressure.
(c)Applicable tank methods. Except as described in § 280.41(a) , any of the methods in § 280.43(e) through (i) may be used if they are designed to detect a release from any portion of the underground piping that routinely contains regulated substances.

40 C.F.R. §280.44