Cal. Code Regs. tit. 8 § 2340.12

Current through Register 2024 Notice Reg. No. 14, April 5, 2024
Section 2340.12 - Mechanical Execution of Work

Electric equipment shall be installed in a neat and workmanlike manner.

(a) Unused openings in boxes, raceways, auxiliary gutters, cabinets, equipment cases, or housings shall be effectively closed to afford protection substantially equivalent to the wall of the equipment.
(b) Conductors shall be racked to provide ready and safe access in underground and subsurface enclosures that persons enter for installation and maintenance.
(c) Internal parts of electrical equipment, including busbars, wiring terminals, insulators, and other surfaces, shall not be damaged or contaminated by foreign materials such as paint, plaster, cleaners, abrasives, or corrosive residues.
(d) There shall be no damaged parts that may adversely affect safe operation or mechanical strength of the equipment, such as parts that are broken, bent, cut, or deteriorated by corrosion, chemical action, or overheating.

Cal. Code Regs. Tit. 8, § 2340.12