From Casetext: Smarter Legal Research

Walter Family Grain Growers, Inc. v. Foremost Pump & Well Servs., LLC

Court of Appeals of Washington, Division 3.
Mar 24, 2022
506 P.3d 705 (Wash. Ct. App. 2022)

Opinion

No. 37915-9-III

03-24-2022

WALTER FAMILY GRAIN GROWERS, INC., Appellant, v. FOREMOST PUMP & WELL SERVICES, LLC, Defendant, Inland Power & Light Co.; and Mitchell, Lewis & Staver Co., Respondents.

George M. Ahrend, Luvera Law Firm, 457 1st Ave., Nw, P.O. Box 816, Ephrata, WA, 98823-0816, for Appellant. Scott Christopher Cifrese, Jeremy Michael Zener, Paine Hamblen LLP, 717 W Sprague Ave., Ste. 1200, Spokane, WA, 99201-3905, for Respondents.


George M. Ahrend, Luvera Law Firm, 457 1st Ave., Nw, P.O. Box 816, Ephrata, WA, 98823-0816, for Appellant.

Scott Christopher Cifrese, Jeremy Michael Zener, Paine Hamblen LLP, 717 W Sprague Ave., Ste. 1200, Spokane, WA, 99201-3905, for Respondents.

PUBLISHED OPINION

Staab, J. ¶ 1 Walter Family Grain Growers (Walter) installed new irrigation and power equipment on its farm that failed, resulting in lost crops. In addition to filing suit against the installation companies, Walter sued Inland Power & Light Company (Inland) for negligence, asserting that excessive voltage service destroyed the equipment. The trial court dismissed Walter's negligence claims against Inland, finding Walter's evidence of breach of duty insufficient to survive summary judgment. We reverse, holding that industry standards and regulations alone do not set a utility's duty of care in a tort, and Walter's evidence is sufficient to raise a material issue of fact on whether Inland breached its duty of care.

BACKGROUND

¶ 2 Since Walter's negligence claim was dismissed on summary judgment, the following facts are set forth in a light most favorable to Walter.

¶ 3 Walter Farms leased property in Lincoln County. Inland provided 3 phase 480-volt power to the Walter property from April 2012 to 2014. Inland tries to push power at 480 volts plus or minus five percent per American National Standards Institute (ANSI) recommendations. Low voltage is a class of nominal system voltages of 1,000 volts or less. Nominal system voltage in a low voltage system is 480 on a three-wire three-phase system. However, nominal utilization voltage is 460 volts on a 480 system.

"Three-phase three-wire systems are systems in which only the three-phase conductors are carried out from the source for connection of loads. The source may be derived from any type of three-phase transformer connection, grounded or ungrounded. Three-phase four-wire systems are systems in which a grounded neutral conductor is also carried out from the source for connection of loads." Clerk's Papers (CP) at 175 (American National Standards Institute (ANSI)).

¶ 4 Power companies maintain service power at 480 volts that attenuates due to customer use and bleeds off to a level of 460 volts at customer utilization points, which is why equipment rated at 460 volts is recommended. Maximum service voltage is 504 volts. ANSI standards allow for 10 percent power fluctuations for temporary conditions. Inland admits that spikes above 506 can happen, and it is not uncommon for a spike to occur for 2/60th of a second. Any spike longer than that or higher than 600 volts, Inland's system would need to be shut off for safety but they would not know to do so.

¶ 5 Prior to 2019, Inland could not monitor or record the voltage in its electrical lines and relied on customers to alert them to problems such as something burned. Lightning arrestors at the substations and poles prevent transmission of huge voltages by blowing out. Inland's transformer is 10 feet from Walter's service meter. Inland rebooted the Walter service meter in April 2013. Colley Walter of Walter Farms did not remember any power problems prior to 2015.

¶ 6 In 2014, Walter contracted with Foremost Pump & Well Services LLC (Foremost) to install a used irrigation pump and new variable frequency pump drive (VFD). The pump was 14 years old, but a pump can be expected to function for 60 years. Walter then applied for an electrical subsidy through Inland for its upgraded VFD equipment. The Foremost contract called for a 300 horsepower pump using incoming phase 3 power of 480 volts and an attached VFD pump control system compatible with the pump to provide constant water pressure. A VFD converts power and emits it back out to the pump motor in pulses. It has an internal fault mechanism that alarms and shuts the drive down when there is too much voltage so that the VFD does not burn out. The VFD was rated for 3 phase 460 volts nominal voltage and can handle up to 485 volts.

¶ 7 The VFD creates "noise" known as harmonic current and sends this current back up the power grid. To prevent this from happening, most power companies require a harmonic filter to be installed with a VFD. The VFD that Walter purchased was ordered with a harmonic filter in it. The harmonic filter built into the VFD adds 8 to 12 volts to the system.

In its reply brief at summary judgment, Inland asserted that unlike most power companies, it did not require the harmonic filter on the VFD, but did not cite to any part of the record to support this factual claim. On reconsideration, Walter submitted the declaration of Roy Jensen, owner of Foremost, who declared that Inland required the harmonic filter. Inland has not repeated this claim on appeal.

¶ 8 Inland turned off the service in May 2014, while Foremost performed the pump installation. At the same time, Jim Klopmeyer of Mitchell, Lewis & Staver (MLS) installed the VFD, electrical control relay, and other components connected to the VFD system. The relay is separate from the VFD. The relay has a threshold for excess voltage. The record does not contain voltage ratings for the control relay or other components except that the relay feeds 120 volts into the harmonic filter. There is no fuse or trip between the relay and the service to prevent excess voltage from burning the relay. If the relay burns, power proceeds directly into the VFD and pump and they would burn and fail after a short period. In summary, power feeds through the electrical system in the following order:

1. Inland South Creston substation.

2. Inland transformer.

3. Inland service entrance and breaker.

4. MLS control power transformer.

5. MLS control relay.

6. Foremost VFD and harmonic filter.

7. Water pump motor.

¶ 9 A year after it was installed, Walter began experiencing electrical problems with the pump. The VFD exhibited repeated error codes indicating " ‘DC Bus Overvoltage’ " which caused the pump to shut down and deprive the crops of water. Clerk's Papers (CP) at 97. The first error code occurred on May 5, 2015. There was no evidence of moisture damage or burn damage to the pump. The pump was unlikely to fail from age. There is nothing in the record suggesting other Inland customers experienced problems at the same time or weather conditions that could cause temporary power service fluctuations.

¶ 10 On May 14, 2015, Walter complained to Foremost and MLS, who investigated the problem. On May 18, 2015, James Klopmeyer from MLS drove out to Walter's site. He pulled up the VFD alarm log and noticed several "trips" on the DC bus over-voltage alarm. He went through the programming parameter settings and visually inspected the unit and wiring. He then used a fluke meter to measure incoming voltage on the input terminals of the VFD "downstream" from the harmonic filter, which was turned off at the time. The measure was at 496 volts. His opinion was that the power was too high for the unit, and he recommended that Walter contact Inland. Once a VFD shuts down, it must be manually reset, and the breaker must be turned on and off. Klopmeyer got the system up and running and watched the power levels for two hours. With the harmonic filter active, his measurements remained at 496 volts.

A fluke meter is a digital voltage measuring device with a positive and negative probe that measures between phase-to-phase or to ground and tells you the voltage. CP at 209.

¶ 11 Colley Walter from Walter called Inland. They came out the same day and indicated that the voltage was "good on their end." CP at 283. Six hours later, the VFD indicated another DC fault code.

¶ 12 On May 19, 2015, Colley Walter called Inland and Foremost. Mr. Jensen of Foremost responded and personally checked the Walter equipment before the Memorial Day weekend while the Inland employees were on site. He did not see any problems with the relay himself, but based on comments by James Klopmeyer, he thought that a "fluttering relay" could cause the harmonic filter to create high voltages. CP at 249. On May 21, 2015, Inland placed a remote voltage meter on the Walter property. The next day, the VFD fault coded again. Inland employee Ver Don Nelson saw spike measurements of 510 volts once or twice and expects that those were taken from the transformer next to the Walter breaker. No voltage measurements were taken from the substation that feeds the Walter property. ¶ 13 The following Saturday, May 23, 2015, Mr. Jensen returned to the Walter property and personally measured voltage of 498 volts, "about" 500 volts, coming in from the service. He also observed voltage readings on the VFD panel. Inland employee "Mike" arrived at the same time and measured the same voltage amount. Mike turned the power down. The pump was turned on and ran. It shut down again due to another DC fault on May 24, Memorial Day weekend.

¶ 14 The next Thursday after Memorial Day, May 26, Mr. Jensen met with Ver Don Nelson of Inland, Mr. Jessup, and Mr. Walter at the Walter property. They saw voltage measurements of 470 to 475 approximately measured on the breaker side. Inland denied anything was wrong and "bumped up" the voltage close to 480. Mr. Nelson did not do this from the office. He increased the voltage by calling Mike Andriola, the Inland engineer. Ver Don Nelson did not say when he did this, but Mr. Walter and Mr. Jensen's depositions evidence establish the date. The VFD shut down again for a DC fault code that night.

¶ 15 On May 27, during his second visit, Mr. Klopmeyer from MLS discovered that Walter's control relay was burned. He testified that a relay is designed to burn up when there is elevated voltage. There were no loose connections. He removed the damaged relay and replaced it with a new one. He re-measured incoming voltage at 482. In his opinion, elevated voltage caused the relay to burn at some earlier time. Mr. Klopmeyer admitted at deposition that the VFD could have been defective but did not think that the relay was defective.

¶ 16 The pump motor failed again in August 2015. It took a week to replace the motor, during which crops died due to 100-degree weather. Foremost employees discovered that the pump had a grounding condition because the ground wires were burnt. Foremost employees attributed the burnt wires to a high voltage surge. Mr. Jensen speculated that it might have been a relay failure or lightning.

¶ 17 Walter sued Foremost and MLS for defective equipment installation. Walter sued Inland for negligently participating in "repairing the irrigation equipment." CP at 61. MLS alleged that Inland provided excessive service voltage.

¶ 18 Following discovery, Inland moved for summary judgment dismissal, arguing that Walter's evidence was insufficient to support the elements of negligence. In its reply briefing, Inland argued for the first time that it did not require the harmonic filter, that it never turned down the power, and that the VFD was incorrectly rated at 460 volts. The summary judgment hearing took place on October 6, 2020. Walter indicated settlement with Foremost and MLS that day. The court granted summary judgment dismissal in favor of Inland. Walter's motion for reconsideration was denied. Walter appeals.

ANALYSIS

¶ 19 Walter contends that the trial court erred in dismissing its negligence claim on summary judgment.

1. NEGLIGENCE

¶ 20 To prove negligence, a plaintiff must show (1) the existence of a duty to the plaintiff, (2) a breach of that duty, (3) a resulting injury, and (4) the breach is a proximate cause of the injury. Hurley v. Port Blakely Tree Farms L.P. , 182 Wash. App. 753, 773, 332 P.3d 469 (2014) (citing Crowe v. Gaston , 134 Wash.2d 509, 514, 951 P.2d 1118 (1998) ). "The existence of a duty is a question of law, while breach of duty and proximate cause are generally questions of fact for the jury." Briggs v. Pacificorp , 120 Wash. App. 319, 322, 85 P.3d 369 (2003) (citing Hertog v. City of Seattle , 138 Wash.2d 265, 275, 979 P.2d 400 (1999) ). Duty has three facets: (1) who owes the duty, (2) to whom, and (3) what is the standard of care. Gall v. McDonald Indus. , 84 Wash. App. 194, 202, 926 P.2d 934 (1996). "Once it is determined that a legal duty exists, it is generally the jury's function to decide the foreseeable range of danger, thus limiting the scope of that duty." Briggs , 120 Wash. App. at 322, 85 P.3d 369.

2. STANDARD OF REVIEW

¶ 21 Summary judgment rulings are reviewed de novo, undertaking the same inquiry as the trial court. Hertog , 138 Wash.2d at 275, 979 P.2d 400. Summary judgment is appropriate when the record demonstrates no genuine issue of material fact. Id . ; CR 56(c). Facts and reasonable inferences are made in the light most favorable to the nonmoving party. Id . For the purpose of negligence, breach and proximate cause may be determined as a matter of law where reasonable minds could not differ. Id . Once a moving party establishes this initial burden, the nonmoving party must rebut the moving party's contentions by setting forth specific facts showing there is a genuine issue for trial. Seven Gables Corp. v. MGM/UA Entm't Co ., 106 Wash.2d 1, 13, 721 P.2d 1 (1986) ; CR 56(e).

¶ 22 A plaintiff must establish an issue of material fact as to each element of negligence to defeat a motion for summary judgment dismissal. Martini v. Post , 178 Wash. App. 153, 164, 313 P.3d 473 (2013). The plaintiff need not prove causation to an absolute certainty. Gardner v. Seymour , 27 Wash.2d 802, 808, 180 P.2d 564 (1947). It is sufficient if the evidence leads a reasonable person to conclude, more probably than not, that harm happened in such a way that the defendant should be held liable. Id . Contributory negligence may also come into play as a question of fact for a jury. Amant v. Pac. Power & Light Co ., 10 Wash. App. 785, 794, 520 P.2d 181 (1974), aff'd , 84 Wash.2d 872, 529 P.2d 829 (1975).

3. EXPERT WITNESSES

¶ 23 As a preliminary matter, we address Inland's argument that Walter cannot prove negligence because evidence of the standard of care and breach will require expert testimony, and Walter has failed to disclose any expert witnesses. The evidence relied on by Walter to counter Inland's motion on summary judgment included the deposition and declaration testimony of Roy Jensen, the owner of Foremost, and James Klopmeyer, a technician from MLS. These witnesses testified as both factual witnesses and experts on how the pumps work and the cause of Walter's electrical issues. Inland did not move to strike the testimony of these witnesses as unqualified under ER 702, and the trial court made no such evidentiary rulings. Therefore, the evidence is before this court, and we consider it to determine whether Walter's evidence is sufficient to carry its burden past summary judgment.

For purposes of our decision, we do not consider the subsequent declaration of Roy Jensen submitted by Walter on reconsideration.

4. DUTY OF CARE AND THE REGULATION OF ELECTRICAL UTILITIES

¶ 24 The parties dispute the nature of Inland's duty to Walter. Inland argues that the standard of care is set by ANSI standards adopted in the Washington Administrative Code (WAC). Walter argues that the standard of care is the same as every other negligence action: that of a reasonably prudent person under the circumstances presented.

¶ 25 This issue was decided by the Supreme Court in Scott v. Pacific Power & Light Co. , 178 Wash. 647, 35 P.2d 749 (1934). There the court held that, "The care to be exercised by an electric company with respect to its wires is such as a reasonably careful and prudent person, having in view the dangers to be avoided and the likelihood of injury therefrom, would exercise under the circumstances in, order to prevent injury." Id . at 649, 35 P.2d 749. The degree of care will vary depending on the foreseeable danger presented by the utility's activity. Id . at 649-50, 35 P.2d 749. For example, high voltage cases in excess of 5,000 volts call for the highest degree of care, while lesser nonlethal voltage found in homes with 120-volt service requires only ordinary care. Brashear v. Puget Sound Power & Light Co. , 100 Wash.2d 204, 210-11, 667 P.2d 78 (1983) (cable TV installer electrocuted by 120-volt lamp on power pole and reviewing court upheld jury verdict that utility violated ordinary duty of care to warn but installer also contributorily negligent).

¶ 26 This court reaffirmed the standard established in Scott in Keegan v. Grant County Public Utility District No. 2 , 34 Wash. App. 274, 280, 661 P.2d 146 (1983). In Keegan , the plaintiffs alleged the electric utility was negligent in maintaining trees under power lines near their home. When the wind blew a power line down, it started a fire that destroyed the plaintiff's home. The Keegan court acknowledged that, "One of the factors to be considered in determining whether a utility has satisfied its duty of care is the practical operation of the utility." Id . at 280, 661 P.2d 146. The extent of evidence relating to a utility company's practical operations is commensurate with the standard of care applied under the circumstances. Id . at 281, 661 P.2d 146. "If the danger posed to the public is minimal, then the utility should be afforded considerable latitude in presenting evidence of its practical operation." Id .

¶ 27 Here, a 480-volt service is low voltage and of minimal danger. Therefore ordinary negligence applies instead of the heightened negligence advocated by Walter. In addition to the low voltage, the specific circumstances presented by this case concern damage to equipment. While Walter argues that these lines could cause death or serious injury under different circumstances, the standard is what a reasonably prudent person would do under these circumstances.

¶ 28 Inland argues that the standard of care is set by applicable regulations and points to the declaration of its expert in support of its argument. Eric Jackson provided a declaration simply stating that utility companies are "governed by the American National Standard Institute and Institute of Electrical and Electronics Engineers (ANSI/IEEE) standards." CP at 104. Other than citing Mr. Jackson's declaration and the regulations themselves, Inland does not cite any authority to support its position that the standard of care is set by the regulations. Notably, since 1986 Washington has eliminated negligence per se for the violation of a regulation but allows the violation of a regulation to be considered as evidence of negligence. See RCW 5.40.050 ("A breach of a duty imposed by statute, ordinance, or administrative rule shall not be considered negligence per se, but may be considered by the trier of fact as evidence of negligence."). It stands to reason that "compliance with applicable statutes and regulations may be used to show a municipality met its duty of care." Fite v. Mudd , 19 Wash. App. 2d 917, 932, 498 P.3d 538 (2021).

¶ 29 The cases cited by the parties support this conclusion. In Hurley , decided in 2014, a logging company argued that compliance with regulations and industry standards shielded them from liability for negligence as a matter of law where logging on steep slopes caused landslides. 182 Wash. App. at 773-75, 332 P.3d 469. The court held that compliance with regulations and industry standards does not per se excuse a defendant from a claim of negligence or entitle a defendant to summary judgment. Id . However, since there was no dispute of material fact, summary dismissal was granted where the logging company was found to have complied with its duty of reasonable care because the geology and hydrology of landslides was outside its knowledge and expertise. Id . Hurley is distinguishable because while loggers are not expected to understand geology, Inland is expected to understand electricity and take safety precautions as an electric utility.

¶ 30 In Celiz , the court applied the highest degree of care due to the power company's placement of high-voltage electrical wires. Celiz & Sanchez’ Estates v. Pub. Util. Dist. No. 1 of Douglas County , 30 Wash. App. 682, 685, 638 P.2d 588 (1981) (summary judgment reversed in part where dispute of material fact existed as to whether utility should have anticipated human contact with low hanging wires charged with 13,200 volts causing death). The utility argued that compliance with former WAC 296-44-316 establishing wire height clearances was prima facie evidence of full compliance with the heightened duty of care identified by the court. Celiz & Sanchez’ Estates , 30 Wash. App. at 686, 638 P.2d 588. The court held that "compliance with electrical standards set forth in the Washington Administrative Code does not mean a lack of negligence; rather, it means compliance with our State's minimal requirements," and such compliance merely precludes a showing of per se negligence. Id. ; see also Crane & Crane, Inc. v. C&D Elec., Inc ., 37 Wash. App. 560, 567, 683 P.2d 1103 (1984) (Violation of the National Electrical Code is not negligence per se.). "The duty of care exercised by an electrical power company is more than mere mechanical skill in compliance with minimal State requirements; it also includes an element of foresight." Celiz & Sanchez’ Estates , 30 Wash. App. at 686, 638 P.2d 588.

¶ 31 While compliance with applicable regulations is relevant to the question of negligence; it is not dispositive. A simple statement indicating that a party has complied with industry customs is not necessarily determinative of negligence where the duty of reasonable care is distinct from such customs. Ranger Ins. Co. v. Pierce County , 164 Wash.2d 545, 553, 192 P.3d 886 (2008) (duty of care breached despite compliance with industry custom). Whether or not reasonable care has been used is generally for a jury. Scott , 178 Wash. at 651, 35 P.2d 749.

5. EVIDENCE IN SUPPORT OF BREACH OF DUTY

¶ 32 Both parties argue the quality of evidence supporting a breach of duty. Walter argues that circumstantial evidence establishes the breach effectively, if not explicitly. Inland argues that expert testimony as to breach is required, and there is no evidence that Inland violated the regulations or its duty.

¶ 33 Circumstantial evidence of negligence may be presented as long as it affords room for " ‘reasonable minds to conclude that there is a greater probability that the conduct relied upon was the [cause in fact] of the injury than there is that it was not.’ " Martini , 178 Wash. App. at 165, 313 P.3d 473 (alteration in original) (internal quotation marks omitted) (quoting Hernandez v. W. Farmers Ass'n , 76 Wash.2d 422, 426, 456 P.2d 1020 (1969) ).

¶ 34 As Walter points out, there is no direct evidence of the line voltage except when specifically measured because Inland did not monitor or record voltage in its lines. Walter argues that the burns to their control relay could not have occurred absent negligence by Inland in providing excessive current from its service. Walter settled with Foremost and MLS without admission of liability, and the trial court never reached the issue of whether their equipment installation caused Walter's pump injury. However, the equipment installed by Foremost and MLS was downstream from Walter's burned control relay, which was fed by the service in the exclusive control of Inland. Walter asserts that its equipment was adequately rated for the electrical service ordered and did not contribute to the incident. Inland disputes this, but the record supports that the 460-volt pump was properly rated for a 480-volt service given industry standards. Finally, much like in Wells v. Nespelem Valley Elec. Coop., Inc. , 13 Wash. App. 2d 148, 157, 462 P.3d 855, review denied , 196 Wash.2d 1027, 476 P.3d 576 (2020), nothing in the record supports the presence of outside factors such as weather justifying power spikes outside the five percent range.

¶ 35 Inland argues that there is no evidence of breach because there is no evidence that it violated applicable regulations. However, as we noted above, evidence of compliance is relevant to breach but not dispositive. Inland's evidence of compliance can be used to counter Walter's circumstantial evidence of a breach, but on summary judgment, it simply creates a material issue of fact.

¶ 36 Even if we were to consider Inland's evidence of compliance, it is insufficient for a court to find lack of breach as a matter of law. While Inland argues that there is no evidence that the power supplied by Inland exceeded regulation standards, it bases this assertion on the application of exceptions to the standards without demonstrating that exceptions applied under the circumstances in this case.

¶ 37 For instance, Inland argues that WAC 480-100-373 and ANSI industry standards allow electrical service to fluctuate within five percent of the nominal 480-volt range, with temporary fluctuations up to 10 percent under certain circumstances. WAC 480-100-373 sets regulations for standard voltage and permissible variation. "Electric utilities must maintain the voltage on their distribution system reasonably constant and any allowed variation must be a gradual change in voltage as a result of normal changes in load." WAC 480-100-373(2). "Voltage variations may not be more than five percent above or below the standard voltage adopted; and (b) [t]he total voltage variation from minimum to maximum may not exceed eight percent of the standard voltage." WAC 480-100-373 (2)(a)(b). This regulation provides for exceptions when voltage variations are "caused by the action of the elements" or due to operation of a customer's equipment start up or emergencies. WAC 480-100-373(3).

¶ 38 Despite conceding two occasions where voltage exceeded the five percent range, and without providing evidence of circumstances required to justify exceptional voltage fluctuations, Inland argues that it operated within industry regulations and standards and thus complied with its duty of care.

¶ 39 Inland also argues that the exception available to rural power utilities applies. Under WAC 480-100-373(2)(b) :

A utility may also permit greater voltage variations in an area where the revenues received do not justify close voltage regulation. In such cases, electric utilities must provide the best voltage regulation that is economically and technically practicable under the circumstances.

This exception is only available under certain circumstances. Inland fails to point to any evidence demonstrating that the specific circumstances existed in this case to support this exception. Inland additionally fails to provide any information regarding economic and technical practicability in the service area where Walter is located.

¶ 40 In Kaech v. Lewis County Public Utility District No. 1 , the reviewing court upheld the jury verdict that the utility violated ordinary care when it exposed cattle to stray low voltage but reversed the damage amount. 106 Wash. App. 260, 270-72, 23 P.3d 529 (2001). Lay evidence showed that the plaintiff detected stray voltage in his barn and complained to the utility. Id . at 271-72, 23 P.3d 529. The utility investigated the claim and discovered a possible insulator problem. Id. at 272, 23 P.3d 529. One utility employee offered to replace the insulators, but another told the plaintiff that there was no stray voltage. Id . Two years after the initial complaint, the Public Utility District (PUD) replaced insulators, finally solving the stray voltage problem. The evidence was sufficient to support a finding that the PUD departed from the standard of care and negligently responded to the plaintiff's repeated complaints. Id . at 271-72, 23 P.3d 529.

¶ 41 The present case is similar to Kaech in that Walter complained to Inland of high voltage, 496 volts, measured on his farm on several occasions. On two occasions, Inland employees measured power in excess of 504 volts, outside the five percent standard variance. Taking the evidence in the light most favorable to Walter, one utility employee turned the power down to mitigate the problem, and then another employee turned the power up a few days later and denied the existence of any problem. In addition, Walter's evidence raises a material issue of fact as to whether Inland had notice of excessive voltage and a potential problem, which in turn impacts the foreseeability of the damage and the scope of Inland's duty. This issue should not have been determined on summary judgment.

6. PROXIMATE CAUSE

¶ 42 Finally, Inland argues that Walter has failed to present evidence sufficient to raise a material issue of fact on proximate cause. Inland's theory is that Walter's evidence is insufficient because it fails to rule out other reasons for the damage to its irrigation system. Inland did not raise lack of evidence on proximate cause as a basis for its motion on summary judgment, and the trial court did not rule on this element of negligence. In its reply brief on summary judgment and again on appeal, Inland argues that Walter's pump was incorrectly rated for 480-volt power. However, as Walter points out, the regulations suggest an explanation for the difference, and Inland does not point to any evidence to support its theory of causation. Walter's claims against Foremost and MLS were resolved shortly before summary judgment, but there may be issues of contributory negligence that were not raised before the superior court that also require a jury for resolution.

¶ 43 Because this issue was not raised below, we decline to consider it on appeal. 7. CONCLUSION

¶ 44 Inland owed Walter a duty of ordinary care to supply low voltage electrical power to Walter's irrigation equipment. While compliance with ANSI standards and WAC regulations is evidence of compliance with the standard of care, it is not solely dispositive. When viewed in a light most favorable to Walter, the evidence is sufficient to raise a material issue of fact as to breach of duty.

WE CONCUR:

Siddoway, C.J.

Fearing, J.


Summaries of

Walter Family Grain Growers, Inc. v. Foremost Pump & Well Servs., LLC

Court of Appeals of Washington, Division 3.
Mar 24, 2022
506 P.3d 705 (Wash. Ct. App. 2022)
Case details for

Walter Family Grain Growers, Inc. v. Foremost Pump & Well Servs., LLC

Case Details

Full title:WALTER FAMILY GRAIN GROWERS, INC., Appellant, v. FOREMOST PUMP & WELL…

Court:Court of Appeals of Washington, Division 3.

Date published: Mar 24, 2022

Citations

506 P.3d 705 (Wash. Ct. App. 2022)

Citing Cases

Estate of Torres v. Kennewick Sch. Dist. No 17

Whether or not reasonable care has been used is generally a question for a jury. Walter Fam. Grain Growers,…

Fievez v. State

To "defeat a motion for summary judgment dismissal," the "plaintiff must establish an issue of material fact…